Pipe Size Calculator
find the pipe diameter you need from flow rate (GPM or CFM)
Enter a flow rate, pick the velocity your system can live with, and get the minimum bore in inches and millimetres — rounded up to the nearest standard NPS with a Schedule 40/80 velocity check.
Pipe size calculator
Flow and velocity in — minimum bore and the nearest standard NPS out.
US gallons per minute — water and other liquids.
Minimum required bore
1.57 in
= 39.8 mm internal diameter
Nearest standard pipe (≥ required)
1 1/2" NPS · DN40
The sizing decision path
Every pipe sizing question arrives as one of four knots. Untie the one you are stuck on — each node below jumps straight to the section or answer that resolves it.
Know your flow?
GPM, LPM or CFM — the one number every sizing decision hangs on.
Resolve it Decision KnotWater or compressed air?
Same bore formula, completely different velocity targets.
Resolve it Decision KnotHave a velocity limit?
Suction 3 · branch 5 · main 8 · short run 10 ft/s.
Resolve it Decision KnotNeed a Sch 80 check?
Thicker wall, smaller bore, higher velocity at the same flow.
Resolve itWhere sizing questions come from — share of the questions this page answers
Editorial estimate of the question mix behind water pipe sizing and air line sizing requests — not measured traffic data.
Pipe size charts: GPM, CFM and schedule
The same engine behind the calculator, pre-tabulated. Required bore is the exact internal diameter the velocity target demands; the NPS column is the smallest standard Sch 40 pipe whose real bore clears it — always rounded up, never down.
GPM to pipe size chart
| Flow (GPM) | At 5 ft/s | At 8 ft/s | At 10 ft/s |
|---|---|---|---|
| 5 | 0.64 in → 3/4" | 0.51 in → 1/2" | 0.45 in → 3/8" |
| 10 | 0.90 in → 1" | 0.71 in → 3/4" | 0.64 in → 3/4" |
| 20 | 1.28 in → 1 1/4" | 1.01 in → 1" | 0.90 in → 1" |
| 30 | 1.57 in → 1 1/2" | 1.24 in → 1 1/4" | 1.11 in → 1 1/4" |
| 50 | 2.02 in → 2" | 1.60 in → 1 1/2" | 1.43 in → 1 1/2" |
| 100 | 2.86 in → 3" | 2.26 in → 2 1/2" | 2.02 in → 2" |
| 200 | 4.04 in → 5" | 3.20 in → 4" | 2.86 in → 3" |
| 400 | 5.72 in → 6" | 4.52 in → 5" | 4.04 in → 5" |
Bore in inches; NPS is the smallest standard size with a Sch 40 bore at or above the requirement. 5 ft/s suits branches, 8 ft/s mains, 10 ft/s short runs.
Compressed air: CFM pipe size at 20 ft/s
| Flow (CFM std) | Required bore (in) | Required bore (mm) | Nearest NPS (DN) |
|---|---|---|---|
| 25 | 1.95 | 49.6 | 2" (DN50) |
| 50 | 2.76 | 70.2 | 3" (DN80) |
| 100 | 3.91 | 99.3 | 4" (DN100) |
| 200 | 5.53 | 140.4 | 6" (DN150) |
Sized at the 20 ft/s air-main default (typical band 15-25 ft/s), treating standard CFM as actual flow at the pipe.
Sch 40 vs Sch 80 velocity check — 30 GPM through 1-1/2 inch pipe
| Schedule | Bore ID (in) | Flow area (ft²) | Velocity at 30 GPM | Vs 5 ft/s branch limit |
|---|---|---|---|---|
| Sch 40 | 1.610 | 0.0141 | 4.7 ft/s | OK — within limit |
| Sch 80 | 1.500 | 0.0123 | 5.4 ft/s | High velocity |
Same 1.900 in outside diameter, different wall: the heavier schedule gives up bore, and velocity rises by the area ratio — about 15% here.
Why pipe sizing is a velocity decision
Flow rate alone never determines a pipe size — it only determines a relationship. The same 30 GPM will happily pass through a 1-1/4 inch line at 6.4 ft/s, a 2 inch line at 2.9 ft/s, or a garden-hose bore at a scream. For any flow you name, there is a whole family of diameters that will carry it. What separates one pipe from the next is how fast the water moves through it, and that is why every serious pipe size GPM calculator, including the one at the top of this page, asks for two inputs and not one. You are not looking up a pipe; you are choosing a velocity and solving for the diameter that delivers it.
The physics behind the choice is the continuity relation: flow rate equals velocity times area. Shrink the area and the velocity must rise to pass the same flow. That single sentence is the entire logic of pipe sizing, and every table, chart and rule of thumb in the trade is a restatement of it.
What velocity actually costs you
Velocity is the currency you spend pipe to save. Push it higher and three bills arrive. Friction loss rises roughly with the square of velocity, so doubling the speed quadruples the pressure you lose per foot — and every pound of that loss is pump energy or shower pressure you never get back. Above roughly 8 to 10 ft/s, water systems start to audibly sing, and a fast-closing valve in a high-velocity line turns momentum into water hammer that can hammer fittings loose over years. Sustained speeds beyond 10-12 ft/s also accelerate erosion, especially at elbows and partial restrictions.
Run velocity too low and the bill changes shape instead of shrinking. Bigger bore means more metal or plastic per foot, a heavier and more expensive install, more volume to fill and drain, and — in lines that stand full — more stagnant water sitting in the wall. Sizing is the art of picking the point on that curve where the trade still makes sense for your service.
Where the ft/s numbers come from
The presets on this calculator — 3 ft/s for suction, 5 for branches, 8 for mains, 10 for short runs, 15-25 for compressed air — are long-standing engineering conventions, not laws of nature. They encode where the cost curves above tend to bend for typical water and air systems. Specifications, codes and experienced owners may move them; a sludge line might insist on 5 ft/s everywhere to keep solids moving, while a short, straight header between two tanks can live at 10. Use the presets as a starting position, then justify any deviation with a friction and noise check rather than a hunch.
The pipe size calculation formula
Rearranging flow equals velocity times area for the diameter gives the pipe size calculation formula used by this page, by every sizing handbook, and by the shortcut constants you may have seen on wall charts.
D = √ ( 4 × Q ⁄ (π × v) )
internal bore diameter = square root of (4 × flow rate ÷ (π × velocity))
The formula is unit-agnostic but not unit-forgiving: Q and v must be in matching units. Work in cubic feet per second and feet per second and D comes out in feet — multiply by 12 for inches. Work in cubic metres per second and metres per second and D comes out in metres. Mixing a GPM input into a ft/s term without conversion is the single most common way to be wrong by a factor of about 450.
Reading the formula term by term
- D is the internal bore diameter — not the nominal size and not the outside diameter. A "2 inch" pipe has a 2.375 in outside diameter and a 2.067 in Sch 40 bore.
- Q is volumetric flow at the pipe. For water, 448.83 GPM equals exactly 1 ft³/s; for air, 1 CFM is 1/60 ft³/s (and 28.32 L/min, or 0.472 L/s).
- v is the mean velocity you have budgeted — the 3 / 5 / 8 / 10 ft/s conventions from the previous section.
For quick mental math the constants collapse nicely. In imperial units, D(in) ≈ √(0.4085 × GPM ÷ ft/s). In metric, D(mm) ≈ √(1273 × L/s ÷ m/s). Both are the same square root with the arithmetic pre-done.
Worked example in imperial units — 50 GPM at 8 ft/s
Convert the flow: 50 ÷ 448.83 = 0.1114 ft³/s. Divide by the velocity budget to get the required area: 0.1114 ÷ 8 = 0.01393 ft². Solve for diameter: D = √(4 × 0.01393 ÷ π) = 0.1332 ft = 1.60 in. The nearest standard pipe whose Sch 40 bore clears 1.60 in is 1-1/2 inch NPS, with a 1.610 in bore — and its actual velocity works out to 7.9 ft/s, squeaking under the 8 ft/s limit with almost nothing to spare. That is the correct answer by the book, but it is also a textbook example of a size that lands exactly on the line: the next size down misses, and any Sch 80 version of the same nominal size will run over.
Worked example in metric units — 1.5 L/s at 1.5 m/s
Required area: 0.0015 ÷ 1.5 = 0.001 m². Diameter: D = √(4 × 0.001 ÷ π) = 0.0357 m = 35.7 mm. Using the metric shortcut: √(1273 × 1.5 ÷ 1.5) = √1273 = 35.7 mm — same answer, one keystroke. A DN40 pipe (NPS 1-1/2 inch, 40.9 mm Sch 40 bore) clears the requirement. Notice how the metric and imperial examples are the same arithmetic wearing different units; the pipe does not care which notebook you write it in.
If you would rather run this in reverse — starting from a known pipe and getting velocity or GPM out — the pipe flow rate calculator is the inverse of this tool and uses the identical dataset.
How to calculate pipe size from flow rate, step by step
Done by hand, sizing a pipe from a flow rate is a five-minute exercise with six steps. The calculator above automates all of them, but knowing the sequence is what lets you sanity-check any result — including this calculator's.
1. Fix the flow number
Decide what flow the pipe must actually carry at its worst moment: peak simultaneous demand, not the sum of every nameplate downstream. A bathroom with a 2.5 GPM shower, a 1.5 GPM faucet and a 1.28 GPM toilet fill does not draw 5.3 GPM in any realistic minute; diversity applies. Undersizing comes from forgetting a future fixture, oversizing from pretending everything runs at once.
2. Pick the velocity limit
Choose from the service conventions: about 3 ft/s on pump suctions, 5 ft/s on small branches, 8 ft/s on mains, 10 ft/s for short transfer runs, 15-25 ft/s for compressed air. When in doubt on a water line, 5 ft/s is the conservative default that rarely disappoints.
3. Run the formula
D = √(4Q/(πv)) with consistent units — or the shortcuts √(0.4085 × GPM ÷ ft/s) in inches, √(1273 × L/s ÷ m/s) in millimetres. This gives the minimum bore the velocity budget allows.
4. Round up to the nearest real bore
Nobody manufactures a 1.57 inch pipe. Take the required diameter to the nearest standard NPS whose actual bore — OD minus twice the wall — is at or above it. Rounding direction is non-negotiable: up. A 4.04 in requirement is not "close enough" to a 4.026 in bore, as the 200 GPM row in the chart above demonstrates.
5. Verify velocity in the actual bore
The standard pipe's bore is rarely the exact diameter you solved for, so recompute velocity as Q ÷ area in the real bore. This is the step skipped most often, and it is where a nominal "pass" quietly becomes an 11 ft/s screamer in a heavier schedule.
6. Check the schedule you will actually buy
Sch 40 and Sch 80 of the same nominal size share an outside diameter but not a bore. If procurement, pressure class or corrosion allowance might steer you to a heavier wall, run the velocity check for that schedule too — the calculator shows both, side by side. Then, before committing, price the friction: the pressure drop page turns your chosen size into psi per 100 ft.
GPM to pipe size: water pipe sizing examples
A water pipe sizing calculator earns its keep on small, everyday numbers, so here are three generic plumbing figures run through the same velocity method. These are engineering illustrations, not installation guidance — local plumbing codes and their fixture-unit tables govern real installations, and where the code minimum and the velocity math disagree, the code wins.
Shower — 2.5 GPM
A modern water-saving showerhead is limited to 2.5 GPM. At a 5 ft/s branch target the required bore is √(0.4085 × 2.5 ÷ 5) = 0.45 in, so a 1/2 inch nominal branch with its 0.622 in Sch 40 bore carries the shower at a placid 2.6 ft/s. There is headroom for the moment the hot and cold taps both open wide — which is exactly why 1/2 inch became the default shower branch long before anyone put a number on it.
Lavatory faucet — 1.5 GPM
A 1.5 GPM basin faucet at 5 ft/s demands only a 0.35 in bore — the arithmetic says a 3/8 inch line could pass it at 2.5 ft/s. Practice keeps fixture branches at 1/2 inch nominal anyway, dropping to the smaller 3/8 inch trim connectors only at the very last foot, because codes set minimum supply sizes and because a faucet that occasionally feeds a bucket deserves margin. The lesson: the velocity method gives the physical floor, and codes and convention set the practical floor above it.
Hose bib — 5 GPM
An outdoor spigot asked to deliver about 5 GPM at a short-run 8 ft/s budget needs √(0.4085 × 5 ÷ 8) = 0.51 in. A 1/2 inch nominal line clears it at 5.3 ft/s actual — comfortably inside the limit, which is why a half-inch hose bib on a half-inch stub never feels starved on a short run but may feel weak fed through fifty feet of it. Length does not change the diameter the velocity picks; it changes the pressure you spend pushing flow through that diameter, which is the subject of the pressure drop check.
Scale the same three-step habit up and the GPM-to-pipe-size chart above is simply these calculations for 5 through 400 GPM, pre-computed at the 5, 8 and 10 ft/s conventions.
Pipe diameter from flow rate and pressure
Search for a way to calculate pipe diameter from flow rate and pressure and you will find the pressure never appears in the formula above — and that is not an omission. Bore size is set by flow and velocity alone. Pressure enters the problem twice, indirectly, and understanding both routes is what separates a sized pipe from a system that works.
The first route is the head budget. Every system has a fixed amount of pressure to spend: the pump's developed head, the static height of a supply tank, the residual at the street main. Friction consumes that budget at a rate that grows roughly with the square of velocity — so pressure decides how much velocity you can afford, and velocity decides the diameter. A system with a fat pressure budget can accept a lively 8-10 ft/s line and a smaller pipe; a gravity feed off a shallow roof tank must creep along at 2-3 ft/s and pay for the bigger bore. Same flow, same formula, very different answer — all because of pressure's indirect role.
The second route is wall selection rather than bore. Higher working pressure does not ask for a bigger pipe; it asks for a thicker one — a heavier Schedule or a pressure-rated plastic class — and a heavier wall quietly shrinks the bore, which feeds back into the velocity check. That loop is why the calculator shows Sch 40 and Sch 80 velocities side by side.
The practical workflow: size the bore from flow and velocity, then verify the pressure you will spend per 100 ft with the pipe pressure drop calculator. If the loss fits the head budget, the size stands; if not, the fix is usually one nominal size up or a velocity target one notch lower.
CFM pipe size calculator: compressed air lines
Compressed air sizing is the same geometry with different etiquette. The bore formula is unchanged — swap GPM for CFM and remember that 1 CFM is 1/60 of a cubic foot per second, or 28.32 L/min (0.472 L/s) if you think metric. What changes is the velocity band: air mains are typically sized for 15-25 ft/s, and this page's CFM mode defaults to 20 ft/s, because air systems fail differently from water systems. Excessive air velocity makes the line howl, but the deeper cost is pressure drop: every psi lost in the main is a psi the compressor must manufacture forever, and air is far more expensive to compress than water is to pump.
One assumption deserves a plain statement, and the calculator makes it too: sizing here treats standard CFM — the flow rate referenced back to atmosphere — as the actual flow at the pipe. In a real 100 psig main, the air is several times denser and its actual volumetric flow is several times smaller than the scfm figure, so scfm-based sizing at 15-25 ft/s lands on the generous, safe side for shop systems. It keeps the sizing purely geometric, which is exactly what a first-pass CFM pipe size calculation should be. Drop legs, dryers and point-of-use plumbing each add their own pressure economics, but the main bore number rarely moves.
The chart above pre-computes the common compressor sizes: 25 CFM lands on 2 inch, 50 CFM on 3 inch, 100 CFM on 4 inch and 200 CFM on 6 inch — all at the 20 ft/s default with Sch 40 bores. Note how forgiving the rounding is at the top end: at 200 CFM the requirement is 5.53 in and the 6 inch bore runs just 15.5 ft/s, well inside the band.
PVC pipe size calculator notes
The most reassuring thing about PVC is that there is no separate math. A PVC pipe size calculator runs the identical bore formula — flow, velocity, square root — because PVC pipe is made to the same iron-pipe-size convention as steel: the same nominal sizes, the same outside diameters, and Schedule 40 and 80 wall families. A 2 inch PVC Sch 40 pipe has a 2.067 in bore, exactly as its steel counterpart does. Everything on this page, including the chart, applies to PVC without modification as long as you use the PVC schedule's actual bore.
The first thing to watch is the Schedule 40 vs 80 split, because PVC Sch 80 is common in chemical and outdoor service and its extra wall costs real bore: 2 inch Sch 80 PVC has a 1.939 in bore against Sch 40's 2.067 in — about 6% less diameter, 12% less area, and therefore 13% more velocity at the same flow. A line sized comfortably at 4.8 ft/s in Sch 40 becomes a 5.4 ft/s line in Sch 80, which matters if 5 ft/s was your limit.
The second watch item is friction, and PVC's advantage there is genuine: with a Hazen-Williams C around 150, a plastic bore is the smoothest wall in common service. That does not change the velocity limit — the ceiling on speed exists for noise, hammer and wear regardless of material — but it does change the pressure bill, which is the subject of the C-value section below.
What the bore math will never tell you is what the material can survive: temperature deratings, sunlight, impact and chemical compatibility are material questions with their own tables, and the manufacturer's pressure class — not this calculator — answers them.
Schedule 40 vs 80 velocity check
Schedule 40 and Schedule 80 pipe of the same nominal size share an outside diameter — that is the whole point of the NPS system — but the 80 wall is thicker, so the 80 bore is smaller, and velocity at a fixed flow rises by exactly the area ratio between the two bores. For 1-1/2 inch pipe: Sch 40 bore 1.610 in, Sch 80 bore 1.500 in, area ratio 1.15 — a 15% velocity penalty for the heavier wall. At 30 GPM that is 4.7 ft/s in Sch 40 against 5.4 ft/s in Sch 80, as tabulated in the chart above.
The example earns its place because of what it does to a borderline size. Against a 5 ft/s branch target, 1-1/2 inch Sch 40 passes and 1-1/2 inch Sch 80 fails — same nominal pipe, opposite verdicts — purely because procurement reached for the heavier wall. If a spec might call for Sch 80 (corrosion allowance, higher pressure class, outdoor impact resistance), run the velocity check for that schedule before committing, and expect to step up one nominal size when the original pick was close to its limit.
The penalty shrinks as pipes grow. At 8 inch NPS the Sch 40 bore is 7.981 in and the Sch 80 bore 7.625 in — a 9% velocity rise for the heavy wall — and at 24 inch it is under 7%. The lesson scales in both directions: the smaller and more borderline the line, the more the schedule decision is a hydraulics decision and not just a strength one.
C-value note: PVC/CPVC vs steel
Velocity decides the bore; the C-value decides what the bore costs you in pressure. The Hazen-Williams coefficient C grades interior smoothness — around 150 for PVC and CPVC, about 120 for new steel, and sliding toward 100 as steel ages, corrodes and tuberculates. Head loss per foot scales with (100/C)^1.85, so small C changes compound steeply: at the same size and velocity, PVC's friction loss is roughly two-thirds that of new steel (a 1.5× advantage to the plastic), and less than half that of tired, corroded steel — a 2.1× advantage.
This is why smoother walls allow smaller pipes for the same loss budget. If your constraint is a pump's available head rather than a noise or wear limit, a C of 150 lets you hold a higher velocity — and therefore buy a smaller bore — while spending the same pressure per foot as a steel line loitering at 5 ft/s. Over long runs this is real money: a thousand feet of main is a thousand chances to shave friction, and plastics collect the dividend every foot of the way.
Two boundaries keep the celebration honest. First, the velocity ceiling does not move: C=150 buys cheaper pressure, not immunity to water hammer, erosion or singing pipes, so the 3/5/8/10 conventions still bind. Second, steel's disadvantage is partly a starting condition — a C=120 new main is not the C=100 main it becomes — so honest steel sizing budgets for the wall it will have in year twenty, not the wall it has on commissioning day. The pressure drop calculator applies these coefficients directly if you want the per-100-ft numbers for your own comparison.
Common mistakes when sizing pipe
Most bad pipe sizes are not exotic failures; they are one of a short list of familiar slips. Each of these shows up in real takeoffs regularly enough to be worth naming.
Adding every nameplate instead of demand
Summing the GPM of every fixture, tool and hose downstream sizes the pipe for a moment that never occurs. Peak simultaneous demand — with diversity factored — is the number the formula wants. Oversizing from inflated flow is the most common sizing error in small systems, and it hides behind the respectable look of caution.
Confusing nominal size, OD and bore
"2 inch" pipe is 2.375 in outside and 2.067 in inside at Sch 40. Feeding the OD into a velocity calculation understates velocity by about 32% at 2 inch — enough to turn a passed check into a failed one the day the real bore arrives.
Rounding down "because it's close"
4.04 in required against a 4.026 in bore is a miss, not a rounding error. The rounding rule is one-directional: up to the next standard bore, always.
Mixing units mid-formula
LPM typed into a GPM field makes the pipe 3.79 times too big; CFM read as GPM makes it 7.48 times too small before the velocity is even considered. Pick one unit family per calculation and convert at the door — or let the unit selector do it.
Ignoring the schedule actually purchased
The Sch 40 check that passed means nothing if the yard delivers Sch 80. Verify velocity in the heavier bore whenever the schedule could change — the calculator's side-by-side rows exist for exactly this reason.
Sizing for today only — or for never
A line sized precisely for this quarter's flow has no room for the second workstation, and a line sized for every imagined expansion wastes money and stagnates. Pick the growth case deliberately, size for it honestly, and stop there.
💡 Tip
Size at 5 ft/s first, then check the result's actual velocity. If it lands under 4 ft/s you may be one nominal size bigger than the flow needs; if it lands over 6, you found the honest size — verify friction before shrinking it.
⚠️ Warning
A pipe sized for today's flow is sized for one year. If expansion is even a possibility — another hose bib, a second workstation, an added tool — decide the growth case now, because the cheapest time to upsize is before the trench is filled.
❌ Don't
Don't size by "bigger is always safer." Oversized lines run slow enough for sediment and scale to settle out, hold more stale water, cost more in material and fittings — and still fail their purpose by depositing the fouling that shrinks their bore anyway.
Frequently asked questions
Concrete numbers for the sizing questions that arrive most often — searchable, expandable, and backed by the same dataset as the calculator.
What size pipe do I need for 30 GPM?Top Question
At a 5 ft/s branch target the required bore is 1.57 in, so 1-1/2" NPS Sch 40 (bore 1.610 in) carries 30 GPM at an actual 4.7 ft/s. At an 8 ft/s main target the requirement drops to 1.24 in and 1-1/4" Sch 40 (bore 1.380 in) works at 6.4 ft/s. One catch: if the line will be Sch 80 and you still hold the 5 ft/s limit, 1-1/2" Sch 80 runs 5.4 ft/s — just over — so step up to 2" Sch 80 (bore 1.939 in, 3.3 ft/s).
How do you calculate pipe size from flow rate?Top Question
Three steps. First convert flow to cubic feet per second (divide GPM by 448.83). Second pick a target velocity — 5 ft/s for branches, 8 ft/s for mains is typical. Third solve D = √(4Q/(πv)) and multiply by 12 for inches. For 50 GPM at 8 ft/s: Q = 0.1114 cfs, so D = 1.60 in, and the nearest standard pipe is 1-1/2" Sch 40 with a 1.610 in bore. Shortcut for water: D(in) ≈ √(0.4085 × GPM ÷ ft/s).
What size pipe for a shower?
A standard 2.5 GPM shower at a 5 ft/s branch target needs a 0.45 in bore, so a 1/2" nominal branch (Sch 40 bore 0.622 in) runs it at a quiet 2.6 ft/s. That is why 1/2" is the default shower branch in most houses. These are generic plumbing figures, not installation instructions — local plumbing codes set fixture supply minimums and always govern the final size.
How many GPM can a 1 inch pipe carry?
It depends entirely on the velocity you accept. A 1" Sch 40 pipe has a 1.049 in bore and about 0.006 ft² of area, so it carries roughly 13.5 GPM at 5 ft/s, 21.5 GPM at 8 ft/s, and 27 GPM at 10 ft/s. For a pump suction held to 3 ft/s the same pipe should only see about 8 GPM. The pipe does not refuse to flow faster — the velocity limit is what protects you from noise, water hammer and friction loss.
How do I size compressed air pipe?
Use the same bore formula with flow in actual cubic feet per second: divide CFM by 60. Keep velocity between 15 and 25 ft/s — this tool defaults to 20 ft/s because air mains are typically sized in that band. At 100 CFM and 20 ft/s the required bore is 3.91 in, so 4" Sch 40 (bore 4.026 in) runs 18.9 ft/s. The stated assumption: sizing is done on standard CFM treated as actual flow, which is conservative and keeps the geometry simple.
Does higher pressure need bigger pipe?
No — bigger pipe comes from more flow or a lower velocity budget, not from pressure. Pressure works in the opposite direction: available head is what pays for friction, so a higher-pressure system can tolerate a higher velocity and therefore a smaller bore. Pressure does pick the wall thickness (the Schedule and pressure rating), just not the bore. Size for flow and velocity first, then check the friction loss per 100 ft with the pressure drop calculator.
Can I use the same sizing math for PVC pipe?
Yes — the bore formula does not know what the pipe is made of. Just use the PVC schedule bore you will actually buy: 2" PVC Sch 40 has a 2.067 in bore, while 2" PVC Sch 80 has a 1.939 in bore, so the same 50 GPM runs 4.8 ft/s in Sch 40 and 5.4 ft/s in Sch 80. The smooth PVC wall (Hazen-Williams C ≈ 150) also halves friction compared with tired steel, which matters for the pressure check, not the velocity limit.
Why does the chart sometimes skip a size?
Because rounding is always up to a real bore, never down. At 200 GPM and 5 ft/s the required diameter is 4.04 in, but a 4" Sch 40 bore is 4.026 in — 0.016 in short — so the correct answer is 5" Sch 40. It looks like a strange skip on paper, but the whole point of a sizing calculator is that 'almost big enough' is not big enough.
What velocity should I use for water pipe sizing?
Common engineering conventions: 2-4 ft/s for pump suction (this tool's preset is 3), about 5 ft/s for branch lines, 6-8 ft/s for mains, and up to 10 ft/s for short transfer runs where friction is not cumulative. Compressed air mains sit at 15-25 ft/s. Lower velocity buys quiet operation and less friction at the cost of pipe; higher velocity saves pipe and pays in noise, water hammer and wear.
How do I convert LPM to GPM for the calculator?
Divide litres per minute by 3.785: 60 LPM is about 15.9 GPM. Or skip the conversion entirely — the calculator's unit selector accepts LPM directly and converts internally (1 L/s = 0.0353147 ft³/s). For fully metric work the shortcut is D(mm) ≈ √(1273 × L/s ÷ m/s): 1.5 L/s at 1.5 m/s needs a 35.7 mm bore, which a DN40 / 1-1/2" pipe clears with a 40.9 mm bore.
Related Resources
Pipe Volume Calculator
Bore capacity of any pipe in gallons, litres, m³ and ft³ — w...
Pipe Flow Rate Calculator
Flow rate, velocity and max flow through a pipe from diamete...
Pipe Pressure Drop Calculator
Darcy-Weisbach pressure drop and friction loss per 100 ft fo...
Gravity Pipe Flow Calculator
Manning equation flow for gravity sewers, storm drains and c...
Air Flow Calculator
CFM flow and pressure drop for compressed air lines — size s...
Thermal Expansion Calculator
Pipe growth from ΔL = α·L·ΔT for steel, copper, PVC and HDPE...
Pipe Dimension Calculator
NPS, DN, OD, ID, wall and circumference in one converter — c...
Reynolds Number Calculator
Reynolds number for any pipe flow from size, velocity and fl...
Pipe Insulation Calculator
Surface area, insulation volume and heat loss for any pipe r...
Square Tube Weight Calculator
Weight of square and rectangular hollow sections from side, ...
Pipe Surface Area Calculator
Pipe outside surface area, cross-sectional area, wetted peri...
Gas Pipe Size Calculator
Size natural gas and propane lines from BTU input — choose p...
Gas Pipe Flow Calculator
Gas pipe flow estimate and BTU capacity pipe size table for ...
Pipe Fitting Weight Calculator
Weight estimate for butt-weld elbows, tees, reducers, caps a...
Pipe Bending Calculator
Pipe bend length, setback, offset and segmented cut angles —...
GPM to PSI Calculator
Convert GPM to PSI pressure drop or calculate GPM from PSI a...
Fittings Pressure Drop Calculator
Equivalent length and friction loss for elbows, tees, valves...
Pipe Wall Thickness Calculator
ASME B31.3 wall thickness from design pressure — hoop stress...
Plastic Pipe Weight Calculator
Weight per foot for PVC Sch 40 and 80, CPVC, HDPE and PEX — ...