Pipe Pressure Drop Calculator
Enter a flow, a pipe and a run length — this calculator solves the Darcy-Weisbach equation with a Colebrook-White friction factor and returns the friction loss per 100 ft in psi for steel, PVC and copper, Reynolds number included, fittings counted.
Pressure drop calculator
Darcy-Weisbach · Colebrook-White friction factor · water
Fittings along the run — each adds K × v²/2g of head
ΣK = 0.00Total pressure drop
0.27 psi
0.62 ft of water head
Straight pipe, per 100 ft
0.27 psi
fittings excluded
Velocity
2.52 ft/s
velocity head 0.099 ft
Reynolds number
69,880
60 °F
Friction factor f
0.0212
Colebrook-White, ε/D 4.47e-4
Flow regime
TurbulentColebrook-White solution
Total loss on 100 ft plus ΣK 0.00, against a 10 psi reference budget (bar caps at 100%).
The equations this page solves
hf = f · (L / D) · v² / 2g + ΣK · v² / 2g
ΔP (psi) = hf (ft) × 0.4331 × SG
with g = 32.174 ft/s², v = GPM ÷ (448.83 × A), Re = v·D/ν, and f from the Colebrook-White relation (f = 64/Re below Re 2,300). In inverse mode the same equation is rearranged to Lmax = (ΔPallow ÷ 0.4331 ÷ (v²/2g) − ΣK) × D / f.
Friction loss by material, side by side
One condition, five walls: 6-inch Sch 40 pipe (6.065 in bore), 100 ft of run, 200 GPM of 60 °F water and no fittings. Velocity is identical in every row at 2.22 ft/s — only the roughness ε changes, and the calculator engine behind this table is exactly the one running above. Even at this gentle flow, a badly corroded wall costs more than twice the loss of smooth PVC.
| Material | ε (ft) | psi per 100 ft | Velocity (ft/s) | Relative loss | Verdict |
|---|---|---|---|---|---|
| PVC (Sch 40) | 0.000005 | 0.120 | 2.22 | RecommendedRecommended — smoothest wall, never corrodes | |
| Copper (Type K/L) | 0.000005 | 0.120 | 2.22 | Excellent — matches PVC, ideal for small lines | |
| Commercial steel | 0.00015 | 0.129 | 2.22 | Standard duty — the baseline for process work | |
| Cast iron | 0.00085 | 0.160 | 2.22 | Legacy systems — verify interior condition | |
| Corroded steel | 0.006 | 0.268 | 2.22 | High RiskMore than double the smooth-wall loss |
Friction factors at this condition: PVC and copper f = 0.0183, commercial steel f = 0.0197, cast iron f = 0.0244, corroded steel f = 0.0408. Reynolds number 92,773 in every row.
Pressure drop reference tables
Pre-computed answers for the three questions that come up most: what a given velocity costs per 100 ft of steel pipe, what each fitting is worth in equivalent straight pipe, and how much pressure elevation alone consumes before any water moves.
Friction loss in Sch 40 steel pipe — psi per 100 ft
Commercial steel (ε = 0.00015 ft), 60 °F water. The GPM column shows the flow that produces each velocity in that bore, so you can enter the row directly into the calculator above. Notice how the small sizes punish you: 1-inch pipe at 5 ft/s loses 5.17 psi per 100 ft, while 6-inch at the same velocity loses 0.59 psi — a factor of almost nine.
| Size | ID (in) | 5 ft/s | 8 ft/s | 10 ft/s | |||
|---|---|---|---|---|---|---|---|
| GPM | psi/100 ft | GPM | psi/100 ft | GPM | psi/100 ft | ||
| 1" | 1.049 | 13 | 5.17 | 22 | 12.55 | 27 | 19.21 |
| 1 1/4" | 1.380 | 23 | 3.66 | 37 | 8.88 | 47 | 13.61 |
| 1 1/2" | 1.610 | 32 | 3.01 | 51 | 7.32 | 63 | 11.22 |
| 2" | 2.067 | 52 | 2.21 | 84 | 5.37 | 105 | 8.22 |
| 2 1/2" | 2.469 | 75 | 1.77 | 119 | 4.30 | 149 | 6.59 |
| 3" | 3.068 | 115 | 1.35 | 184 | 3.29 | 230 | 5.04 |
| 4" | 4.026 | 198 | 0.97 | 317 | 2.36 | 397 | 3.61 |
| 5" | 5.047 | 312 | 0.73 | 499 | 1.79 | 624 | 2.74 |
| 6" | 6.065 | 450 | 0.59 | 720 | 1.43 | 900 | 2.19 |
| 8" | 7.981 | 780 | 0.42 | 1,247 | 1.03 | 1,559 | 1.57 |
| 10" | 10.020 | 1,229 | 0.32 | 1,966 | 0.78 | 2,458 | 1.20 |
| 12" | 11.938 | 1,744 | 0.26 | 2,791 | 0.63 | 3,489 | 0.97 |
Fittings: K values and equivalent lengths
Equivalent length is the straight-pipe run that burns the same head as the fitting: Leq = K·D/f, shown here at a typical turbulent f = 0.02 for three common sizes. On a 6-inch line, one 90° elbow behaves like 22.7 ft of pipe and a basket strainer like 63.2 ft.
| Fitting | K | L/D at f = 0.02 | Equiv. ft — 2 in | Equiv. ft — 4 in | Equiv. ft — 6 in |
|---|---|---|---|---|---|
| 90° elbow | 0.90 | 45D | 7.75 | 15.10 | 22.74 |
| 45° elbow | 0.40 | 20D | 3.45 | 6.71 | 10.11 |
| Tee — branch flow | 1.80 | 90D | 15.50 | 30.19 | 45.49 |
| Gate valve (open) | 0.15 | 7.5D | 1.29 | 2.52 | 3.79 |
| Swing check valve | 2.00 | 100D | 17.23 | 33.55 | 50.54 |
| Basket strainer | 2.50 | 125D | 21.53 | 41.94 | 63.18 |
Static pressure reminder: elevation head
Elevation costs 0.4331 psi per foot whether one gallon per minute is flowing or none at all. This is the pressure component friction can never touch — a capped column of water 100 ft tall still shows 43.31 psi at the bottom.
| Elevation (ft of water) | Static pressure (psi) |
|---|---|
| 1 | 0.43 |
| 2 | 0.87 |
| 5 | 2.17 |
| 10 | 4.33 |
| 20 | 8.66 |
| 50 | 21.65 |
| 100 | 43.31 |
How pipe pressure drop actually works
Everything the calculator does, explained from first principles — the equation, the friction factor, the materials and the traps. No prior fluid mechanics assumed; every number is one you can reproduce in the tool above.
What is pressure drop in a pipe
Pressure drop is the pressure a flowing liquid loses between two points of a pipe run. Push water through a line and every foot of wall in contact with the flow rubs against it, every bend turns the stream on itself, and every valve forces it through a restriction. The energy that rubbing consumes comes out of the pressure — which is why a pump discharge reading of 50 psi can arrive at a fixture 200 ft away as 41 psi even on flat ground. That missing 9 psi is the friction loss in pipe, and sizing any pumping system is really the business of keeping it inside a budget.
Two different mechanisms get lumped under the word pressure, and confusing them causes most field errors. Static pressure exists whether water moves or not — a capped column of water 10 ft tall presses 4.33 psi on its base, full stop. Friction pressure drop exists only when water moves, and it grows with roughly the square of velocity. A pressure drop in pipe calculator like this one computes only the friction part; the static part is a one-line multiplication by 0.4331 psi per foot of elevation. Real systems pay both, which is why the total pressure available at a fixture is supply pressure minus friction minus elevation.
The convention that makes loss numbers comparable is psi per 100 ft. Saying a line loses 2.4 psi means nothing without the length attached; saying it loses 2.4 psi per 100 ft lets you scale to any run by simple multiplication and compare one design against another instantly. Most piping design guides target something between 2 and 5 psi per 100 ft for branch circuits, and much less for long mains.
The Darcy-Weisbach equation explained
The Darcy-Weisbach equation is the physics-based relationship this whole page runs on. In words: the head lost to friction equals the friction factor, times the ratio of run length to pipe bore, times the velocity head. Written compactly, hf = f · (L/D) · v²/2g, with each term doing a specific job. It earns its place as the standard because it is derived from energy conservation rather than fitted to experiments, so it works for any Newtonian fluid — water, glycol, fuel, brine — at any temperature, in any pipe material.
Head loss hf — the answer in feet of water
Head loss is energy expressed as a column of water. If a run comes back with hf = 6.2 ft, that means the flowing water arrives with the same energy it would have if it had climbed 6.2 ft into the air. Multiply by 0.4331 and you get psi; that single conversion is the bridge between the fluid-dynamics world and the gauge world. Head is also the unit pump curves are drawn in, so staying in feet makes pump selection arithmetic trivial.
The friction factor f — where the physics hides
The friction factor is a dimensionless number near 0.02 for turbulent water flow in commercial pipe. It is not a property of the pipe alone: it depends on how fast the water moves (through the Reynolds number) and how rough the wall is relative to the bore (the relative roughness ε/D). A smooth 6-inch plastic line at 2 ft/s and a rusty 2-inch line at 8 ft/s have completely different factors — getting f right is the whole game, and the next section is devoted to it.
Length over diameter L/D — why long thin lines hurt
Loss scales with how many bore-widths the water must traverse. A 100 ft run of 1-inch pipe is 1,200 diameters long; the same 100 ft in 10-inch pipe is only 120. That ratio is why small diameter lines generate brutal losses: 1-inch steel at 5 ft/s burns 5.17 psi per 100 ft while 6-inch at the same velocity burns 0.59 psi. Doubling the diameter cuts the per-foot loss by roughly a factor of thirty at constant flow.
Velocity head v²/2g — the price of speed
Velocity head is the kinetic energy of the stream written as a height of water. At 5 ft/s it is 0.389 ft; at 10 ft/s it is 1.550 ft. Because it grows with the square of velocity, doubling the flow quadruples every loss on the line — pipe friction and fittings alike. This term is also the currency fittings are paid in: a K value of 0.9 means the fitting destroys nine tenths of one velocity head.
From head loss to psi
One foot of water column weighs 0.4331 psi. Multiply total head — straight pipe plus fittings — by 0.4331 and the result is gauge pressure lost. The factor is exact for water at standard conditions; for other liquids multiply instead by specific gravity × 0.4331. Water is SG 1.0, so this page keeps it at 1 and shows the term in the formula for transparency.
Friction factor and the Moody chart
A Moody chart is just a picture of the friction factor: Reynolds number on a logarithmic x-axis, friction factor on the y-axis, one curve for each value of relative roughness ε/D. Pick your Reynolds number, slide up to your roughness curve, read f across. The chart has no formula of its own — it plots the solution of the Colebrook-White equation, which is the calculation this page performs automatically on every keystroke.
The Colebrook-White equation, in words
Colebrook-White says: the friction factor is 0.25 divided by the square of a logarithm, and that logarithm blends two resistances — wall roughness scaled by pipe size (ε over 3.7 D) and viscosity-driven momentum exchange (2.51 divided by Reynolds times the square root of f). The catch is that f appears inside its own logarithm, so you cannot solve it directly. You guess a value, feed it through the right side, get a better value, and repeat until the number stops moving. Engineers used to do two or three hand iterations off a Moody chart; this calculator seeds the loop with the Swamee-Jain approximation and runs 50 fixed-point passes in microseconds, converging to eight decimal places every time.
The smooth pipe limit
As roughness shrinks toward zero — PVC, HDPE and drawn copper at ε = 0.000005 ft are effectively there — the roughness term in the logarithm vanishes and the friction factor depends only on Reynolds number. This is the lowest curve on the chart, the line a moody chart calculator for smooth pipe traces out. It is also the physical floor: no material choice can push turbulent losses below it, which is why the matrix above shows PVC and copper tied at 0.120 psi per 100 ft.
The fully rough limit
At very high Reynolds numbers the viscous term 2.51/(Re√f) becomes negligible and friction depends only on relative roughness — the hydraulically rough regime. Rough old mains live here: the flow is so energetic that the viscous sublayer is thinner than the bumps on the wall, so making the water faster changes nothing about the character of the loss per unit velocity head. Corroded steel at ε/D = 0.0119 sits close to this limit, and its f = 0.0408 barely improves at higher flows.
Laminar and the transition band
Below Reynolds 2,300 the flow is laminar and friction collapses to the exact result f = 64/Re — the straight line on the far left of the chart, with roughness irrelevant. Between 2,300 and 4,000 lies the transition band where the flow flips unpredictably between characters and no correlation is trustworthy. The calculator applies the turbulent formula there and flags the result as transitional so you know the uncertainty. Practical water systems almost never visit this band on purpose.
How to calculate pressure drop in a pipe, step by step
Here is the full manual method, with every intermediate number, for the default condition: 100 GPM through 4-inch Sch 40 commercial steel, 100 ft of run, 60 °F water. Follow along and you can reproduce or audit any result the calculator produces.
- Find the true inside diameter. 4-inch NPS is actually 4.500 in outside diameter with a 0.237 in Sch 40 wall, so the bore is 4.500 − 2 × 0.237 = 4.026 in, or 0.3355 ft. Nominal size is a name, not a measurement — always work from the real ID.
- Compute the flow area. A = π/4 × D² = π/4 × 0.3355² = 0.0884 ft².
- Convert flow and get velocity. 100 GPM ÷ 448.83 = 0.2228 ft³/s. Velocity v = Q/A = 0.2228 ÷ 0.0884 = 2.52 ft/s. Comfortable service velocity.
- Reynolds number. Re = v·D/ν = 2.52 × 0.3355 ÷ 0.0000121 ≈ 69,900 — well into turbulent territory, as almost all working water lines are.
- Relative roughness and friction factor. ε/D = 0.00015 ÷ 0.3355 = 0.000447. Iterating Colebrook-White converges on f = 0.0212.
- Assemble the equation. Velocity head v²/2g = 6.35 ÷ 64.35 = 0.0987 ft. Head loss hf = 0.0212 × (100 ÷ 0.3355) × 0.0987 = 0.62 ft. In psi: 0.62 × 0.4331 = 0.27 psi for the 100 ft run.
Now count the fittings. Suppose the route has four 90° elbows and one open gate valve: ΣK = 4 × 0.9 + 0.15 = 3.75, adding 3.75 × 0.0987 = 0.37 ft. Total loss becomes 0.99 ft, or 0.43 psi — the fittings added 38% to a run that looked like pure pipe. That is precisely the mistake the fittings checklist in the calculator exists to prevent.
Friction loss by material
Roughness is the only material property that enters the Darcy-Weisbach calculation for water duty — the wall does not care about strength or chemistry here, only about how bumpy it is relative to the bore. The families below cover nearly every water line you will meet.
Steel pipe friction loss
New commercial steel rates ε = 0.00015 ft, and in the 6-inch matrix above it loses 0.129 psi per 100 ft at 200 GPM — barely 7% more than plastic. The problem with steel is time, not manufacturing: oxidation and scale grow the effective roughness year by year. Design guides often price in 0.0005 ft for aged steel and 0.006 ft for badly corroded surfaces, which is the 0.268 psi figure — more than double the new-pipe loss at identical flow. If a system must hold its performance for decades, either upsize the steel or specify a lined or coated product.
Copper pipe friction loss
Drawn copper tube is glass-smooth, ε = 0.000005 ft, matching PVC exactly. Where copper differs is scale of use: it lives in the small diameters — half-inch to 2-inch — where the L/D penalty is fiercest. A half-inch branch carrying 6 GPM runs about 10.5 ft/s, and at that speed the loss is roughly 11 psi per 100 ft before fittings. Copper friction loss calculations therefore reward conservative velocity targets of 5–8 ft/s in hot-water recirculation and suction lines, where noise and erosion matter as much as pressure.
PVC pipe friction loss
PVC and HDPE share the ε = 0.000005 ft rating, equivalent to a Hazen-Williams C of about 150. Two practical advantages follow. First, the wall never corrodes or tuberculates, so the friction loss you compute on day one is the loss on day 7,000 — the diameter you buy is the diameter you keep. Second, fused HDPE has no gasket steps or cement joints to add loss. That is why the comparison matrix tags PVC as the recommended water-duty material: 0.120 psi per 100 ft at 200 GPM in 6-inch, the lowest figure any wall can post at that Reynolds number.
Ductile iron and cast iron friction loss
Unlined cast iron starts near ε = 0.00085 ft and gets worse as tuberculation nodules colonize the bore — mains a century old have effectively become smaller, rougher pipes, which is why their pumping bills climbed over the decades. Modern ductile iron solves this with a cement-mortar lining that restores smooth-pipe behavior, and design manuals credit lined ductile iron a Hazen-Williams C of 140 or better. If you inherit an old unlined iron main, measure actual pressure rather than trusting the nameplate diameter: the roughness may have tripled.
Fittings: K values and equivalent length
A fitting is a machine for turning the flow, and turning costs energy. The loss coefficient K expresses that cost in velocity heads: the fitting consumes K × v²/2g. The K values this calculator uses are the standard turbulent-flow figures — 0.9 for a 90° elbow, 0.4 for a 45°, 1.8 for flow through a tee branch, 0.15 for an open gate valve, 2.0 for a swing check and 2.5 for a basket strainer. Notice the pattern: anything that makes water reverse or pass a fine screen (check valve, strainer, tee branch) costs several times what a smooth turn does.
The equivalent-length view makes the same point differently. Divide K by a typical friction factor of 0.02 and the quotient is how many bore-widths of straight pipe the fitting stands in for. On a 6-inch line: one 90° elbow ≈ 22.7 ft, one tee branch ≈ 45.5 ft, one basket strainer ≈ 63.2 ft. Stack up six 90° elbows on a routed main and you have silently added roughly 136 ft of hypothetical straight pipe — more loss than the 100 ft of real pipe between them. Count fittings first; they are rarely rounding errors on anything shorter than a football field.
Pressure in a pipe vs pressure drop in a pipe
These are different questions that share a unit. The pressure in a pipe at rest is static head: 0.4331 psi for every foot of water above the gauge, and nothing else. Flow rate, pipe size and material are all irrelevant until the water moves. This is why a 100 ft tall standpipe reads 43.31 psi at its base with the valve shut, and why a static pressure in pipe calculation is a one-line elevation sum.
Once water flows, you can calculate pressure in a pipe as a budget: total pressure available at any point equals the supply static pressure, minus accumulated friction along the path, minus 0.4331 psi for every foot the point sits above the source (or plus, if it sits below). A fixture fed by a 60 psi main, through 150 ft of line losing 2.1 psi per 100 ft, rising 12 ft, arrives with 60 − 3.2 − 5.2 ≈ 51.6 psi. Subtract the fixture requirement and you know instantly whether the design works.
The search for how to calculate psi in a pipe from flow rate usually means one of two things. If you want the loss, this page computes it directly from flow. If you know the pressure you can afford to spend and want the distance it buys, that is the inverse problem — and it is exactly what Max run length mode solves: given allowable ΔP, flow, diameter and material, it rearranges Darcy-Weisbach algebraically and returns the longest run that stays inside budget. Pressure from flow rate alone is not a well-defined question; pressure lost because of flow rate is.
Reynolds number in plain language
The Reynolds number compares how much momentum the water carries against how sticky it is: Re = v·D/ν, all in consistent units. Momentum smears the flow into chaotic eddies; viscosity layers it into clean sheets. Below Re 2,300 the sheets win — laminar flow, where water slides in order and friction follows the exact law f = 64/Re. Above about 4,000 the eddies win — turbulent flow, where mixing dominates and Colebrook-White takes over. In between, the flow wavers and no formula deserves your trust.
Real water systems live almost entirely in the turbulent region. A single gallon per minute in a half-inch line is already past Re 4,000, and by the time you pump anything serious the number is in the tens of thousands. What changes the value most in practice is temperature: ν falls from 1.66 × 10⁻⁵ ft²/s at 40 °F to 0.74 × 10⁻⁵ at 100 °F, so the same line at the same flow runs at more than double the Reynolds number on a hot day. That is why the calculator asks for water temperature — in the worked 4-inch example the loss shifts from 0.285 psi at 40 °F to 0.252 psi at 100 °F. Small, but free to capture.
Suction side friction loss
The suction side of a pump deserves its own arithmetic because it spends from a different account. Net positive suction head (NPSH) available is the pressure energy at the pump inlet above vaporization — and every foot of suction-side friction subtracts from it directly. A cavitating pump does not lose efficiency gracefully; it sheds head, rattles like gravel is passing through, and erodes its impeller. Suction lines therefore get sized generously: keep the velocity around 3–6 ft/s, keep the run short and straight, and prefer long-radius elbows.
The numbers show why. A 3-inch steel line moving 100 GPM runs 4.34 ft/s — fine for suction. Now add the usual hardware: one 90° elbow and a swing check valve, ΣK = 2.9. At a velocity head of 0.293 ft those fittings cost 0.85 ft, about 0.37 psi, on top of straight-pipe friction. On a discharge side that is trivial; on a suction side with the source only a few feet below the impeller, it can be the difference between quiet operation and cavitation. Compute the suction run separately, and if the total suction loss plus static lift gets anywhere near the pump's NPSH requirement, upsize the line a size or two.
Why a live calculator beats a spreadsheet
A lot of searches look for a pipe pressure drop calculator Excel file, and the reason is understandable: engineers already live in spreadsheets. The trouble is the friction factor. Colebrook-White is implicit — f hides inside its own logarithm — so a plain formula cell cannot produce it. You are left enabling iterative calculation with circular references, driving Goal Seek row by row, or pasting in VBA macros that break the moment the file leaves your machine. Each workaround is fragile in a different way, and none of them tolerates the quick what-if that sizing work actually consists of.
This page runs the full 50-pass fixed-point iteration in JavaScript on every keystroke — along with Reynolds number, regime detection, fitting summation and the inverse length solve. There is nothing to install, nothing to enable, and it behaves identically on a phone in the plant walkway. When you do need the result in a spreadsheet, the Copy results button hands you a tidy text block with every intermediate value, ready to paste next to your pump curve. Spreadsheets are excellent ledgers; they are poor solvers for implicit equations.
Worked examples
A 6-inch main at 200 GPM
200 GPM in 6-inch Sch 40 steel (6.065 in bore) gives 2.22 ft/s — a deliberately gentle main. The engine returns Reynolds 92,773, ε/D = 0.0003 for steel (about 0.00001 for PVC), friction factor 0.0197 for commercial steel, velocity head 0.077 ft, and 0.30 ft of head loss per 100 ft — 0.13 psi. The same flow in PVC costs 0.120 psi per 100 ft, and in badly corroded steel 0.268 psi. Add six 90° elbows (ΣK 5.4) and they contribute 5.4 × 0.077 = 0.41 ft, roughly another 0.18 psi. Verdict: a healthy main with headroom; even the corroded-wall case stays under a third of a psi per 100 ft at this velocity.
A 2-inch branch at 12 GPM
12 GPM through 2-inch Sch 40 steel (2.067 in bore) runs at 1.15 ft/s — quiet, residentially calm. Reynolds number 16,330, f = 0.0289, velocity head a mere 0.0205 ft. Straight-pipe loss is 0.34 ft per 100 ft, about 0.15 psi. Take a realistic 30 ft branch with two elbows and a check valve (ΣK = 3.8): total loss 0.18 ft, or 0.08 psi. The branch costs almost nothing — this is what an oversized, low-velocity distribution line looks like, and it is the cheapest insurance a system can buy.
💡 Tip
Match the temperature before comparing runs. The same 4-inch line at 100 GPM loses 0.285 psi per 100 ft of cold 40 °F water but only 0.252 psi at 100 °F — a 12% swing you get for free by picking the right viscosity. For hot-water recirculation loops, always calculate at service temperature, not at the mains value.
⚠️ Warning
This page covers fluid-side pressure loss only — how much pressure water gives up to friction as it moves. It does not answer how much internal pressure the pipe wall can safely hold; that is a material-strength question handled by Barlow's formula. For wall ratings by schedule and material, use the dedicated pressure rating tool in the calculators hub.
❌ Don't
Don't ignore fittings. Six 90° elbows on a 6-inch main are worth about 136 ft of straight pipe at typical turbulence — on a 100 ft run, the fittings out-lose the pipe. And don't reach for Hazen-Williams outside water duty: it is an empirical fit to water at ordinary temperatures and has no physical basis for glycol, brine or fuel. Darcy-Weisbach travels; Hazen-Williams does not.
Pipe pressure drop: frequently asked questions
Short, numeric answers to the questions this page is searched for. Every figure can be reproduced in the calculator above.
How do you calculate pressure drop in a pipe?
Use the Darcy-Weisbach equation: multiply the friction factor f by the length-to-diameter ratio L/D and by the velocity head v²/2g. That product is the head loss in feet of water; multiply by 0.4331 to convert to psi, then add fitting losses (ΣK × v²/2g). Worked numbers: 100 GPM in 4-inch Sch 40 steel over 100 ft gives v = 2.52 ft/s, Re ≈ 69,900, f = 0.0212, head loss 0.62 ft and 0.27 psi of pressure drop. The calculator on this page does every step live.
What is the friction loss in a 4 inch pipe per 100 feet?
It depends on flow. In Sch 40 commercial steel at 60 °F: 100 GPM (2.5 ft/s) loses about 0.27 psi per 100 ft; 198 GPM at 5 ft/s loses about 0.97 psi; 317 GPM at 8 ft/s loses about 2.36 psi; and 397 GPM at 10 ft/s loses about 3.61 psi. Loss climbs roughly with the square of velocity, which is why the same pipe can be nearly free at one flow and punishing at another.
How do you calculate psi in a pipe?
Separate the two components. Static pressure depends only on elevation: 0.4331 psi per foot of water column, so a 20 ft tall standpipe shows 8.66 psi at its base even with zero flow. Friction pressure exists only while water moves and comes from Darcy-Weisbach. Pressure available at a fixture equals supply static pressure, minus friction along the path, minus 0.4331 psi for every foot the fixture sits above the source.
What is the Darcy-Weisbach equation?
It is the physics-based equation for friction loss in pipe: hf = f × (L/D) × v²/2g. hf is head loss in feet, f is the dimensionless friction factor, L/D compares run length to bore, and v²/2g is the velocity head. Example: f = 0.0212, L/D = 298 (100 ft of 4-inch pipe) and v²/2g = 0.099 ft multiply out to 0.62 ft of head, or 0.27 psi. Unlike the empirical Hazen-Williams fit, it works for any Newtonian fluid.
How do you calculate friction factor?
For laminar flow (Re below 2,300) it is exact: f = 64/Re. For turbulent flow, solve the Colebrook-White relation f = 0.25 / [log10(ε/(3.7D) + 2.51/(Re√f))]². Because f appears inside its own logarithm, you iterate: seed with the Swamee-Jain approximation, feed the result back in, and repeat until it stops moving — this calculator runs 50 fixed-point passes in a few microseconds. At Re = 69,900 and ε/D = 0.00045 it converges on f ≈ 0.0212.
How much pressure do fittings lose?
Each fitting adds K × v²/2g of head. At 5 ft/s the velocity head is 0.389 ft, so one 90° elbow (K = 0.9) costs 0.35 ft ≈ 0.15 psi and a basket strainer (K = 2.5) costs 0.97 ft ≈ 0.42 psi. Expressed as equivalent length at f = 0.02, a 90° elbow is worth about 45 diameters — on a 6-inch line that is 22.7 ft of straight pipe, so six elbows behave like an extra 136 ft of run. Count the fittings; they are not rounding errors.
How do you calculate water pressure from flow rate?
Flow rate does not set the pressure in a pipe — it sets how fast pressure is lost. What you can calculate from flow is the friction component: velocity from Q/A, Reynolds number, friction factor, then psi per 100 ft. If you actually know the allowable loss instead, solve the inverse problem: 5 psi of allowance for 100 GPM in 4-inch steel supports roughly 1,850 ft of pipe with no fittings. That is exactly what the Max run length mode on this page computes.
Which pipe material has the lowest friction loss?
Smooth plastics and drawn copper tie for first place: PVC, HDPE and copper all use ε = 0.000005 ft. In the reference matrix on this page (6-inch pipe, 200 GPM, 100 ft), PVC and copper lose 0.120 psi per 100 ft, commercial steel 0.129, cast iron 0.160 and badly corroded steel 0.268 — more than double the smooth-wall figure at the same flow. Material choice matters most in small diameters and long runs.
Does water temperature change the pressure drop?
Yes, through viscosity. Warm water is thinner, so the Reynolds number rises and the friction factor falls slightly. For 100 GPM in 4-inch Sch 40 steel over 100 ft: at 40 °F the loss is 0.285 psi, at 60 °F it is 0.270 psi, at 80 °F it is 0.260 psi and at 100 °F it is 0.252 psi. The effect is modest in turbulent flow but real — pick the temperature closest to your service water.
Related Resources
Pipe Volume Calculator
Bore capacity of any pipe in gallons, litres, m³ and ft³ — w...
Pipe Flow Rate Calculator
Flow rate, velocity and max flow through a pipe from diamete...
Pipe Size Calculator
Find the right pipe diameter from flow rate and velocity — G...
Gravity Pipe Flow Calculator
Manning equation flow for gravity sewers, storm drains and c...
Air Flow Calculator
CFM flow and pressure drop for compressed air lines — size s...
Thermal Expansion Calculator
Pipe growth from ΔL = α·L·ΔT for steel, copper, PVC and HDPE...
Pipe Dimension Calculator
NPS, DN, OD, ID, wall and circumference in one converter — c...
Reynolds Number Calculator
Reynolds number for any pipe flow from size, velocity and fl...
Pipe Insulation Calculator
Surface area, insulation volume and heat loss for any pipe r...
Square Tube Weight Calculator
Weight of square and rectangular hollow sections from side, ...
Pipe Surface Area Calculator
Pipe outside surface area, cross-sectional area, wetted peri...
Gas Pipe Size Calculator
Size natural gas and propane lines from BTU input — choose p...
Gas Pipe Flow Calculator
Gas pipe flow estimate and BTU capacity pipe size table for ...
Pipe Fitting Weight Calculator
Weight estimate for butt-weld elbows, tees, reducers, caps a...
Pipe Bending Calculator
Pipe bend length, setback, offset and segmented cut angles —...
GPM to PSI Calculator
Convert GPM to PSI pressure drop or calculate GPM from PSI a...
Fittings Pressure Drop Calculator
Equivalent length and friction loss for elbows, tees, valves...
Pipe Wall Thickness Calculator
ASME B31.3 wall thickness from design pressure — hoop stress...
Plastic Pipe Weight Calculator
Weight per foot for PVC Sch 40 and 80, CPVC, HDPE and PEX — ...
Part of the Pipe Calculator toolset — free, in-browser, and no sign-up. Browse all calculators